Mains supply | 230V 50/60Hz. |
Mains rated current | 350mA maximum. |
Internal power supply | 19V-28.5V (27V nominal). Ripple 7V maximum |
Total output current limited to | 1.5A @ 230Vac (ImaxA eq 146mA) |
Quiescent current | 25mA (mains failed, internal sounder active, PSU & gen fault LED lit) |
Max battery size and type | 2 x 12V 3.2Ah VRLA connected in series. Min. battery size 1.2Ah. |
No. of detector zone circuits | 8 (Max. length per circuit is 500m) |
Call point resistor value | 470 to 680Ω. |
Max. devices per detector zone | 25 detectors (or 32 detectors/manual call points combined). |
No. of conventional sounder circuits | 4 (Max. length per circuit is 500m). |
EOL resistor value | 6800Ω 5% Tol 0/25W (blue, grey, red, gold) |
Alarm voltage | 27V max, 20V min (final battery voltage) |